75F Central Control Unit (CCU)
The 75F Central Control Unit (CCU) is the on-site brain of the 75F platform: a wall-mounted tablet, building management interface, and gateway to the 75F cloud. It aggregates zone data from 75F terminal devices, makes AHU control decisions, and provides a modern touchscreen for facility teams.
Request a Quote
Description
Product Overview
- Model: 75F Central Control Unit (CCU)
- Function: Wireless building management hub and AHU/rooftop supervisor
- Interface: 8" 1200 × 800 touchscreen tablet with Android-based UI
- Role: Connects 75F Smart Nodes, HyperStats, and sensors to the 75F cloud and coordinates system-level control.
How It Works
- Communicates with field devices over a secure 900 MHz mesh network and RS-485 for Modbus devices.
- Uses Wi-Fi or LAN to connect to the 75F cloud, enabling proactive and predictive control strategies.
- Aggregates zone-level data (temperature, occupancy, airflow, etc.) to optimize AHU and equipment operation.
- Supports operation with or without an active cloud connection, maintaining core control locally.
Key Features
- Controls single and multi-stage systems, heat pumps, fan coils, air handlers, and more.
- Supports up to 48 terminal equipment modules per CCU for scalable deployments.
- Built-in scheduling, setpoint adjustments, and live trend graphs on the touchscreen interface.
- Alerts and events with severity color coding for quick diagnostics.
- Removable tablet with secure magnetic alignment and locking slider for easy service.
The CCU combines the role of a traditional supervisory controller and an applied equipment controller in one device, simplifying architecture while enhancing visibility for owners and operators.
Quick Specs
- Display: 8" 1200 × 800 touchscreen
- Power: 24 V AC/DC (5 VA typical, 20 VA max)
- Operating Temp: 32–122 °F (0–50 °C)
- Communications: 900 MHz mesh, BLE 4.1, Wi-Fi, RS-485 sensor bus
- Inputs: (2) 0–10 V analog, (2) 10 kΩ thermistor
- Outputs: (4) 0–10 V/4–20 mA analog, (7) 24 V DC/1 A relays
- HVAC Control: Up to 5 stages of heating/cooling, up to 5 fan stages, 0–10 V valve output, dehumidifier/humidifier
- Mounting: Wall plate over standard electrical junction box